|
|
Rate
Schedules and Policies
RSP
K-1
K.
Connection of Customer Facilities
Standard
Service Voltages
Maritime Electric's electric service is provided in the form
of alternating current at a frequency of 60 Hertz (cycles
per second).
The nominal service voltages are:
Standard single-phase service:
Secondary voltage:
Standard
three-phase service and combination single-phase and three-phase
service:
Secondary voltage:
-
120/208
volts, wye connected
-
347/600
volts, wye connected
Primary
voltage, as available:
Maritime Electric provides primary service at a variety
of voltages. Customers requesting primary service should make
application to the Company to determine the voltage available.
Customers desiring service at nonstandard voltages provide all
the necessary facilities to convert a standard service voltage
to the desired utilization voltage.
Where two or more Maritime Electric lines are available to serve
the customer's load requirements, Maritime Electric will determine
from which line service will be provided to the customer.
RSP
K-2
Connection
of Customer Facilities
Delivery
Point
Maritime Electric makes all connections to the
delivery point and specifies the delivery point as being one
of the following:
-
The
point of connection of the customer's service entrance mast
conductors to Maritime Electric's Overhead Secondary Service
at the weatherhead;
-
The
point of connection of the customer's Underground Secondary
Service to Maritime Electric's secondary voltage system;
-
The
secondary bushings of Maritime Electric's transformer;
-
The
primary bushings of the customer's transformer;
-
The
primary side of the customer's main disconnect switch located
in the customer's electrical vault (existing customers only,
not available to new customers);
-
The
load side of Maritime Electric's fuse disconnect;
-
The
source side of the customer's disconnect switches;
-
The
source side of the customer's switchgear located at the
customer's premises;
-
The
load side of the primary metering unit; or- Any other point
specified by Maritime Electric.
Service Entrance Equipment
Service entrance equipment standards are specified in the publication
"Electrical Installation Requirements" issued by the
Electrical and Elevator Inspection Branch of the Planning and
Inspection Services Division of the Department of Community Affairs
and Attorney General of the Province of Prince Edward Island.
Metering
Equipment
Metering equipment is part of Maritime Electric's facilities supplied
to customers.
RSP
K-3
Connection
of Customer Facilities
Metering equipment, except as noted below, is installed
on the low voltage side of the transformer. General Service
and Small Industrial Customers are primary metered under
any of the following circumstances:
-
Service entrance size exceeds 2000 amps;
-
The customer requests that the transformer
be placed indoors; or
-
The customer requires a voltage that is
not a Maritime Electric standard service voltage.
Large Industrial Customers are normally metered
at a primary voltage of 69kV; if they are metered at a voltage
below 69kV, readings are adjusted for the associated transformation
losses.
Service
to Multiple Buildings
Normally, Maritime Electric installs a meter for each individual
building of a premises except as follows:
A group of adjacent buildings located on the same property served
by one electric service is accepted by Maritime Electric as one
customer for billing purposes if the buildings:
The
meter may be installed at either a primary or secondary voltage
level. The customer must supply, install, own and maintain all primary
and/or secondary facilities beyond the delivery point.
Specific applications of a maypole or primary voltage supply are
specified in the following sections.
Secondary Voltage Supply/Maypole Service
The delivery point is generally at the maypole on the customer's
property at a secondary voltage. The maypole, conductors from Maritime
Electric facilities to the maypole, the anchor and metering equipment
are Maritime Electric facilities. Maritime Electric makes all connections
at the maypole.
RSP
K-4
Connection
of Customer Facilities
The
customer will make connection(s) to buildings, leaving
a sufficient length of wire at the maypole to allow connection
to Maritime Electric facilities. Customer facilities include
the secondary services, attachment hardware on the load
side of the delivery point, the conduit and meter socket,
and all equipment on the maypole except metering equipment.
If the maypole subsequently has to be replaced, Maritime
Electric must first disconnect the facilities. The customer
is responsible for the maintenance and transfer costs
of the pole mounted service entrance equipment.
Primary Voltage Supply
A primary voltage supply may be run by Maritime Electric
to a pole or structure on the customer's property. The
delivery point is the load side of the primary metering
unit. Connections at the delivery point will be made by
Maritime Electric.
Primary conductors and equipment up to the delivery point
including the metering equipment are Maritime Electric
facilities. All facilities beyond the delivery point are
customer facilities.
Overhead
Secondary Service or Underground Secondary Service
Maritime
Electric designates the point on its facilities where the Overhead
Secondary Service or Underground Secondary Service originates.
|
|